Digital timer TDE4-3/12-24V
T=(0.1sec ... 9999min), Us=12÷24V ac/dc, Output 4A/220V, 95x49x113mm
The TDE4-3/12-24V digital timer is a microprocessor device which is used for switching off and on electrical circuits for a fixed time interval "T" in the range from 0.1sec to 9999min set programmatically. The timer can be started in three ways: a) by turning on the supply voltage; b) by pressing a button on the front panel of the timer; c) by using an external button or sensor connected to the timer. The time-relay has an energy-independent memory. The digital timer is designed for installation in a dashboard (panel montage).
FEATURES
The TDE4-3 digital timer is a compact device on the basis of microprocessor. Used to switch direct current and alternating current electric circuits for a fixed time interval "T", which is set in digital form. The time relay has two operating modes LOG1 (_I¯I_) and LOG2 ( _I¯ ), which allow it to be used in various automated systems. It is used widely in automation of production, technological and other processes.
TECHNICAL PARAMETERS
Digital indication, LED - red | 4 digits, h = 14mm (height) |
Time range, T | 0,1 sec … 9999 min |
Supply voltage, Us | 12÷24V ac/dc (11÷31Vdc / 11÷27Vac) |
Power consumption, P | 2 W (85 mA) |
Output - Relay (NO+NC) | 4A / 220VAC |
Error counting time | ±0,05 % |
Operating temperature, Tamb | -20º...+50º C |
Degree of protection | IP40 |
Joining | Terminal block |
Overall dimensions | 95х49х113 mm |
Programmable parameters
Parameter, T | 0.1 ÷ 999.9 (1 ÷ 9999) |
Range of parameter T : | |
0,1÷999,9 sec | 0.1'' |
1 ÷ 9999 sec | 1.0'' |
1 ÷ 9999 min | 1.0' |
Operating mode (summation / subtraction) | Inc / dEc |
Interruption of the supply voltage Us : | |
- after an interruption, the reading continues from the current data | Cont |
- after an interruption, the reading automatically starts from the beginning | Full |
- after an interruption, a stop mode of the current data is established | Ucc |
- after an interruption, the timer is reset | Goto |
Automatic start when the power is turned on for the first time | no / Auto |
Mode of operation ( _⌈‾⌉_ / _⌈¯ ) | LOG1 / LOG2 |
Timing diagram of the TDE4-3 timer
Timing diagram of the output relay (“NO” - normally open contact)
Schemes of connection
Fig.1
Starting the timer with NPN sensor
Fig.2
Starting the timer with switch K2
Overall dimensions (mm)
Short description
The TDE4-3 digital time relay is an electronic device used as a means of automating production processes. Used for switching direct current and alternating current electrical circuits.
Documentation
Typical parameters of TDE4-3 timer
TYPE | SUPPLY VOLTAGE | CONSUMPTION |
---|---|---|
TDE4-3 / 12-24V | 11÷31VDC / 11÷27VAC | 2W (85mA) |
TDE4-3 / 220V | 220VAC ±10% | 4W (16mA) |